In brief
Fault code U1 on Mitsubishi Electric Ecodan PUHZ HW140VHA2 BS PUHZ HW140YHA2 BS Service Manual OC means: Fault code U1 indicates abnormal high pressure detected during compressor operation, triggered by the opening of the high-pressure switch 63H (threshold at 4.15 MPa). This anomaly can result from hydraulic circuit problems, insufficient air circulation or electronic failures in the outdoor unit. Most common cause: The main cause is the activation of the high-pressure switch 63H during compressor operation. This can be due to reduced water flow, fouling of heat exchangers, blockage of the pump or outdoor fan, short cycling, or a failure of the control circuit. First action: Inspect the water flow, check if the water pipe filter is blocked, if the plate heat exchanger is fouled, if the pump is blocked or faulty.. Call a registered engineer if the fault returns after basic checks or involves refrigerant work (F-Gas registered engineer required).
According to the Mitsubishi Electric service manual, the U1 code is triggered when the high-pressure switch 63H opens at a threshold of 4.15 MPa.
U1 • Mitsubishi Electric • Ecodan PUHZ HW140VHA2 BS PUHZ HW140YHA2 BS Service Manual OC
Fault code U1 Mitsubishi Electric: causes, diagnosis and solution
Fault code U1 indicates abnormal high pressure detected during compressor operation, triggered by the opening of the high-pressure switch 63H (threshold at 4.15 MPa). This anomaly can result from hydraulic circuit problems, insufficient air circulation or electronic failures in the outdoor unit.
Source: Mitsubishi Electric documentation (service manual – according to product reference)

Équipe Ask Marcel
Techniciens CVC certifiés
Rédaction et validation terrain par des installateurs PAC, clim et chauffage. Données croisées avec plus de 50 000 fiches pannes documentées.
What does fault code U1 on Mitsubishi Electric mean?
Fault code U1 indicates abnormal high pressure detected during compressor operation, triggered by the opening of the high-pressure switch 63H (threshold at 4.15 MPa). This anomaly can result from hydraulic circuit problems, insufficient air circulation or electronic failures in the outdoor unit.
The main cause is the activation of the high-pressure switch 63H during compressor operation. This can be due to reduced water flow, fouling of heat exchangers, blockage of the pump or outdoor fan, short cycling, or a failure of the control circuit.
Symptômes
- Compressor stops due to activation of the protection device.
- Fault code U1 displayed on the unit.
- Inspection code blinking on the LED3 display of the outdoor unit.
- System stops operating.
- Measurable high pressure in the refrigerant circuit.
Diagnostic
1. Check the hydraulic circuit and circulation
- Inspect the water flow, check if the water pipe filter is blocked, if the plate heat exchanger is fouled, if the pump is blocked or faulty.
- Check if the pipework is blocked or broken, and if there is short cycling of the outdoor unit.
2. Inspect the outdoor unit and components
- Check if the outdoor fan is blocked or faulty, and if the outdoor heat exchanger is fouled.
- Check the temperature detected by the outdoor temperature thermistor using the outdoor unit monitoring function (SW2) to detect an incorrect reading.
3. Electronic diagnosis and connection
- Isolate the power supply and check if code F5 appears on restart to confirm an open 63H connector.
- Check the connection of the 63H connector on the control board, the condition of the board itself and the operation of the linear expansion valve.
How to reset fault code U1 on Mitsubishi Electric?
Start by checking and repairing any defects in the hydraulic circuit (flow, filter, pump, pipework). Then inspect the outdoor unit for fouling, fan blockage or short cycling. If the problem persists, check the electrical connections of the 63H switch and replace the outdoor control board if necessary.
When should you call an F-Gas engineer?
This code appears during normal compressor operation if the refrigerant circuit pressure exceeds the safety threshold of 4.15 MPa. It is frequently linked to hydraulic circulation problems (pump, flow) or thermal blockage of the outdoor heat exchanger, preventing expansion of the
Affected models
- PUHZ HW140VHA2 BS
- PUHZ HW140YHA2 BS
- PUHZ SW50VKA BS
- PUHZ W50VHA BS
Field context
This code appears during normal compressor operation if the refrigerant circuit pressure exceeds the safety threshold of 4.15 MPa. It is frequently linked to hydraulic circulation problems (pump, flow) or thermal blockage of the outdoor heat exchanger, preventing expansion of the
Technical source data
The U1 code signals abnormal high pressure (>4.15 MPa) during compressor operation, activating the 63H switch. Causes include reduced water flow (blocked filter, blocked or faulty pump), fouling of heat exchangers (indoor/outdoor), obstructed or broken pipework, short cycling of the outdoor unit, or an outdoor thermistor reading error (Extract 1, 2, 3). The diagnostic procedure separates hydraulic checks (codes 1-5) from outdoor unit checks (codes 6-7 to 0). If the fault persists after a power cut, an F5 display on the control board indicates an open 63H connector, requiring connection checks or board replacement (Extract 1, 2, 3, 5).
Sources: Ecodan ATW PUHZ W50VHA BS Service — ecodan-atw-puhz-w50vha-bs-service.pdf (p. 16) · Ecodan PUHZ SW50VKA BS Service Manual OCH525C — ecodan-puhz-sw50vka-bs-service-manual-och525c.pdf (p. 22) · Ecodan PUHZ HW140VHA2 BS PUHZ HW140YHA2 BS Service Manual OCH439N — ecodan-puhz-hw140vha2-bs-puhz-hw140yha2-bs-service-manual-och439n.pdf (p. 55)
Questions fréquentes
What are the main hydraulic circuit causes for a U1 code?
According to the manuals, check the following points: reduced water flow, blocked pipe filter, fouled plate heat exchanger, blocked or faulty water pump, and obstructed or broken pipework. These faults prevent proper fluid circulation, leading to high pressure detected by the 63H switch (Extract 1, 2, 3).
How do I diagnose an outdoor thermistor reading error?
A faulty outdoor thermistor can detect a temperature lower than actual, causing a U1 code. To check, access the outdoor unit monitoring function via switch SW2 (position 1) and observe the temperature displayed on the LED3 indicator. If the value is abnormally low, the thermistor must be replaced (Extract 1, 2, 3, 5).
What does the F5 display mean after a power cut?
If the U1 code persists, isolate the power supply and restart the unit. If code F5 appears, it specifically indicates that the yellow connector of the 63H switch is open or poorly connected. Check the electrical connections on the outdoor control board or replace it if the problem persists (Extract 1, 2, 3).
Besoin d'aide pour ce diagnostic ?