In brief

Fault code U1 on Gree sapphire service manual 18mbh and 24mbh models a means: Fault code U1 indicates a failure of the phase current detection circuit for the compressor. This fault, classified as a hardware failure, causes the compressor to stop to protect the system. Most common cause: The main cause is the detection of an average offset voltage exceeding 12.5% of 1.65 V on the current detection circuit or the current sensor itself. First action: Observe the display of code U1 on the remote controller or Nixie tube after a 200-second wait.. Call a registered engineer if the fault returns after basic checks or involves refrigerant work (F-Gas registered engineer required).

According to the Flexx Ultra R32 service manual (page 52), the system judges the fault if the average offset voltage exceeds 12.5% of 1.65 V within 1 second of power-up.

U1Greesapphire service manual 18mbh and 24mbh models a

Gree fault code U1: causes, diagnosis and solution

Fault code U1 indicates a failure of the phase current detection circuit for the compressor. This fault, classified as a hardware failure, causes the compressor to stop to protect the system.

Source: Gree documentation (service manual – according to product reference)

Équipe Ask Marcel

Équipe Ask Marcel

Techniciens CVC certifiés

Rédaction et validation terrain par des installateurs PAC, clim et chauffage. Données croisées avec plus de 50 000 fiches pannes documentées.

What does fault code U1 on Gree mean?

Fault code U1 indicates a failure of the phase current detection circuit for the compressor. This fault, classified as a hardware failure, causes the compressor to stop to protect the system.

The main cause is the detection of an average offset voltage exceeding 12.5% of 1.65 V on the current detection circuit or the current sensor itself.

Symptômes

  • Display of code U1 on the remote controller or Nixie tube after 200 seconds.
  • Compressor stops during cooling and dehumidification cycles, while the indoor fan continues to run.
  • Complete unit shutdown during heating cycles.
  • Indicator flashing (ON 0.5s / OFF 0.5s) on some models.

Diagnostic

1. Check the code and system behaviour

  • Observe the display of code U1 on the remote controller or Nixie tube after a 200-second wait.
  • Check system behaviour: the compressor should stop in cooling mode (indoor fan active) and the entire unit should stop in heating mode.

2. Analyse the detection circuit

  • Confirm that the average offset voltage exceeds 12.5% of 1.65 V within 1 second of power-up.
  • Identify the fault as being in the current detection circuit or the current sensor.

How to reset fault code U1 on Gree?

Replace the outdoor control board AP1. This part contains the faulty current detection circuit identified as the probable cause in the service manuals.

When should you call an F-Gas engineer?

This code appears during a start-up attempt or during operation, preventing the compressor from running. The outdoor unit LED indicator flashes or displays the code, and the indoor fan behaviour varies by mode (cooling or heating) to indicate the state.

Affected models

  • Sapphire Service Manual 18MBH/24MBH
  • Multi21 Plus 18K/24K
  • Flexx Ultra R32
  • High Static Slim Duct
  • Universal Floor Ceiling
  • Livo Plus 30K/36K

Field context

This code appears during a start-up attempt or during operation, preventing the compressor from running. The outdoor unit LED indicator flashes or displays the code, and the indoor fan behaviour varies by mode (cooling or heating) to indicate the state.

Technical source data

Code U1 signals a hardware failure of the phase current detection circuit for the compressor. The system judges the fault if the average offset voltage exceeds 12.5% of 1.65 V on the circuit or current sensor within 1 second of power-up (flexx-ultra-r32-service-manual-a.pdf). This diagnosis causes immediate compressor shutdown to protect the system: in cooling mode, the indoor fan continues while the compressor stops; in heating mode, the entire unit stops (multi21-plus-service-manual-18k-24k-c.pdf). The identified cause is a current detection error, requiring replacement of the outdoor control board AP1, the part containing the faulty circuit (high-static-slim-duct-service-manual-b.pdf).

Sources: multi21 plus service manual 18k 24k c — multi21-plus-service-manual-18k-24k-c.pdf (p. 24) · flexx ultra r32 service manual a — flexx-ultra-r32-service-manual-a.pdf (p. 52) · high static slim duct service manual b — high-static-slim-duct-service-manual-b.pdf (p. 37)

Questions fréquentes

What is the exact behaviour of the unit when code U1 is active?

When code U1 is displayed, the compressor stops immediately to protect the system. Depending on the operating mode: in cooling or dehumidification, the indoor fan continues to run while the compressor is inactive. In heating mode, the entire unit shuts down completely. This behaviour is observed on the affected Gree models.

What is the precise technical condition that triggers this fault?

Fault U1 is triggered if, after power-up, the average offset voltage detected on the current circuit or sensor exceeds 12.5% of 1.65 V within 1 second. This condition indicates a hardware failure of the current detection circuit or the sensor itself, requiring intervention on the control board.

What is the recommended repair solution for this code?

The repair procedure is to replace the outdoor control board AP1. This component contains the current detection circuit identified as the cause. No other circuit tests are specified in the service manuals to resolve this offset voltage detection issue.