Technical guide

HVAC fault code ambiguities across brands (E, F, H families)

Technicians often assume code equivalence across OEMs. This reference maps 10 codes × 8 brands with manual-backed meanings or an explicit gap — never a guessed equivalent.

Updated 9 September 2026

Method

A cell is filled only when an AskMarcel sheet cites an OEM manual (document id + page when available). Otherwise: not documented. A neighbour code (Samsung E101 vs E6) is not an equivalent. Last verified: 9 Sep 2026.

E6

Never port a Gree bus test onto another brand.

BrandMeaning in corpusSource
GreeRS485 indoor/outdoor loss >60 sFlexx Ultra R32 p.12
MitsubishiSerial UI/UE comms break (S1/S2/S3, Ecodan)Ecodan ATW Databook p.128
DaikinNot documented—
ToshibaNot documented—
HitachiNot documented (03 = transmission, not E6)—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented (E101 = UI/UE comms, different code)E101 sheet

F0

Gree F0 is not a generic « low gas » label.

BrandMeaning in corpusSource
GreeLow-refrigerant / blocked-capillary protectionService Manual F0 Flowchart
DaikinNot documented—
MitsubishiNot documented (U0 = low gas on Mr. Slim)—
ToshibaNot documented—
HitachiNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

E1

Gree E1 (high pressure) ≠ Daikin E1 (outdoor PCB).

BrandMeaning in corpusSource
GreeCondenser high-pressure protection (~4.2 MPa on some GMV)Flexx p.27 / GMV6 p.40
DaikinOutdoor PCB failure (single LED, FTXJ p.56)4PFR769827 p.56
MitsubishiNot documented—
ToshibaNot documented—
HitachiNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

H8

The historical « Altherma 4 » URL documents FTXJ H8 only.

BrandMeaning in corpusSource
DaikinFTXJ: compressor input on OU — Altherma 4 not in this source4PFR769827 p.55
GreeNot documented—
MitsubishiNot documented—
ToshibaNot documented—
HitachiNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

1C

BrandMeaning in corpusSource
ToshibaInverter/compressor drive at start (Digital Inverter)Toshiba Troubleshooting Guide
GreeNot documented—
DaikinNot documented—
MitsubishiNot documented—
HitachiNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

03

Hitachi 03 = UI/UE transmission. Condensate tray is code 01.

BrandMeaning in corpusSource
HitachiUI/UE transmission break (cable 1-2, PCB fuses)Technical Data Wiring & Transmission
GreeNot documented—
DaikinNot documented—
MitsubishiNot documented—
ToshibaNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

P10

BrandMeaning in corpusSource
ToshibaCassette/ducted condensate pump or floatCassette installation manual
GreeNot documented—
DaikinNot documented—
MitsubishiNot documented (P5 is a different family)—
HitachiNot documented (01 = condensate tray)—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

UH

Daikin FXHQ UH ≠ Mitsubishi Ecodan UH.

BrandMeaning in corpusSource
DaikinFXHQ/VRV system fault: outdoor supply, F1/F2 A1P, remote4PFR769827 p.56 ; 4PW05746 p.11
MitsubishiCurrent sensor / U-V-W compressor wiring (Ecodan PUHZ)OCH525C Ecodan PUHZ
GreeNot documented—
ToshibaNot documented—
HitachiNot documented—
AtlanticNot documented—
PanasonicNot documented—
SamsungNot documented—

369 and ERR 60

Two unrelated Atlantic codes.

BrandMeaning in corpusSource
Atlantic 369Alféa / Excellia gas-pressure sensorAtlantic service manual
Atlantic ERR 60Navilink thermostat: batteries, radio or cableNavilink notice
Other 6 brands369 / ERR 60 not documented under these labels—

Panasonic and Samsung have no sourced equivalent for these ten codes in the current blog corpus — an explicit gap is better than an analogy.

Field workflow

1) Brand + exact model. 2) Open that brand's sheet. 3) If the same code exists elsewhere, read that row — do not copy the procedure. 4) « Not documented » means open the model's manual, do not improvise.